Stainless Steel Underfloor Heating Manifold H2004A is mainly used for water distribution in floor heating system, specially designed for optimal heat distribution in floor heating system.
H2004A is a stainless steel floor heating manifold designed for modern and efficient floor heating systems. The top is integrated with a visual water supply flow meter, which is convenient for real-time monitoring and adjustment of the flow of each circuit to ensure uniform heating; the bottom is integrated with a return water control valve for independent adjustment to optimize the hydraulic balance of the system.
The product strictly complies with the EN1264 standard to ensure long-term durability and safety. It adopts a flat-seal external threaded interface, which has strong sealing and easy installation; the low installation depth design saves space and is suitable for a variety of building structures.
The modular accessory system provides high flexibility and can easily expand or adjust the pipeline configuration to meet the needs of different apartment types and projects. With precision quality as the core, H2004A is an ideal distribution hub for residential and commercial floor heating systems.
Precision-engineered Stainless Steel Round Pipe Manifold with flat-sealing male threads, low installation depth, and adaptable modular accessories. Compliant with EN1264, it offers a reliable heating solution with a top-supply flowmeter and bottom-return control valve.
| Dimension | ||
|---|---|---|
| Specification | Ways | L |
| G1″×3/4″ | 2 | 126 |
| G1″×3/4″ | 3 | 176 |
| G1″×3/4″ | 4 | 226 |
| G1″×3/4″ | 5 | 276 |
| G1″×3/4″ | 6 | 326 |
| G1″×3/4″ | 7 | 376 |
| G1″×3/4″ | 8 | 426 |
| G1″×3/4″ | 9 | 476 |
| G1″×3/4″ | 10 | 526 |
| G1″×3/4″ | 11 | 576 |
| G1″×3/4″ | 12 | 626 |
| Technical Data | ||
|---|---|---|
| Material | Manifold body | Stainless steel 304 |
| Port connection | Brass | |
| Seal | EPDM | |
| Working Pressure | 0-10bar | |
| Working temperature | -10℃ to 70℃ | |
| Wokring Media | Water | |
| Flow | 1-5L/Min | |
| Flow tolerance | ±10% | |
| Test precedure | |
|---|---|
| Sealing test | Make water pressure test under 8-10bar and keep for 1min,to make sure there is no leakage |
| High temperature test | Test manifold set under temperature 80℃ enviroment,to make sure there is no leakage and cracking |
| Low temperature test | Test manifold set under temperature -30℃ enviroment,to make sure there is no leakage and cracking |
| Flow test | make sure the tolerance is ±10% |
| flow meter burst pressure test | make burst pressure test under 10Mpa to make sure there is no cracking. |
| insert valve life test | make 100 thousand time using life test there is no broken |